Fire-Smoke-Curtain-Controller

Fire & Smoke Curtain Controller

UL Listed Fire & Smoke Curtain Controller is a vital safety device engineered to efficiently manage the deployment and retraction of UL-listed fire and smoke curtains in response to fire alarm signals. This controller ensures optimal safety and compliance in commercial and industrial environments, providing essential protection against smoke and fire hazards.

Description

UL Listed Fire & Smoke Curtain Controller is a vital safety device engineered to efficiently manage the deployment and retraction of UL-listed fire and smoke curtains in response to fire alarm signals. This controller ensures optimal safety and compliance in commercial and industrial environments, providing essential protection against smoke and fire hazards.

Features

Main Control Unit (NF-FGCP):

  • Centralized management for fire and smoke curtain deployment and retraction.
  • Direct interface with fire alarm systems for prompt emergency response.

Motor Control Unit (NF-FMC):

  • Individual control for each motor, allowing precise management of curtain movements.
  • Effectively manages controlled gravity fail for enhanced safety and reliability.

Integration with BMS:

  • Optional BMS board for enhanced facility management, providing real-time monitoring and control capabilities.

Operational Mechanism:

  • Curtains remain retracted, secured by low-voltage power supplied to the motors.
  • Automatic deployment is initiated upon fire alarm activation.

Fire Alarm Signal Input:

  • Equipped with dual normally closed, volt-free contacts for reliable and secure signal reception, ensuring rapid response.

Specifications

Model

Group Controller: NF-FGCP

Motor Controller: NF-FMC

Certification

UL Listed (S35507)

Compliance Standard

UL 864

Power Supply

120-230 VAC / 50-60 Hz

Maximum Motor Control Capacity

Up to 6 motors (20W each) – (Model: NFGR42/40)

Up to 3 motors (40W each) – (Model: NFGR53/30)

Battery Backup

Up to 12 hours (12V / 7Ah x 2 set).

Integration

Compatible with Building Management System (BMS) via optional integration board (Model: NBMS).

Stage Delays

Features a 2-stage delay with adjustable closing delay for controlled operations.
Manual Test Keys

For manual operation and testing of the system.

Override Function

Optional override features for manual curtain operation.

Resources

 Datasheet Download